In Hot Water For Lack Of Hot Water

At the Kansas City airport Marriott, it’s digital mixing to the rescue.

The lack-of-hot-water problem at the Kansas City Airport Marriott was resolved with the installation of a Powers IntelliStation digital mixing system.

Most hotel managers have learned through experience that their toughest, crankiest customer is an unhappy guest at midnight or five a.m. They’ve either just woken up and have to move out posthaste or, after a long day of travel, they need to turn in immediately. A tense situation can escalate if there’s insufficient pressure–or hot water–for a shower.

Angry hotel guests, at the oddest hours, are known to make quite a ruckus if a hotel’s worst-case scenario coincides with a stressed-out business traveler. “It’s a situation we work very hard to avoid,” admitted Greg Brinkerhoff, director of engineering at the Marriott Kansas City Airport hotel. According to Brinkerhoff, late arrivers and early risers can push the limits of a hotel’s water heaters and plumbing systems. At his 384-room hotel, adjacent to the busy airport, there’s a steady flow of guests at all hours.

“The highest demand for hot water comes between 5 and 6 A.M. and again between 10 P.M. and midnight,” added Brinkerhoff. It wasn’t uncommon for hotel managers to get several calls a week from guests, displeased about the lack of hot water.

“Unfortunately,” said Brinkerhoff, “The best we could tell them at the time was that hot water ‘was on its way.’”

The Powers IntelliStation touchscreen control operates a three-way valve through a high-speed actuator to precisely maintain the selected outlet temperature. Temperature and pressure sensors are included at key points within the panel to enable an immediate response to changes in fixture demand-and-supply water conditions.

Hot-water woes

For more than two years, the hotel battled domestic hot-water issues. As it turned out, a large hydronic valve was used for the original system. The misapplied valve had a 120-sec. response time and couldn’t actuate quickly to keep up with the changing water pressures within the hotel. Because of the valve’s sluggish response time, every time something would go wrong with the pumps, heat exchangers, or storage tanks, the entire domestic-hot-water system would require a time-consuming recalibration. Maintenance was required routinely–a constant source of disruption for the engineering staff.

“More or less, when maintaining the domestic water system, we had to isolate the entire piped network, shutting it down completely,” explained Brinkerhoff. “Whenever the hot-water mixing valve opened or modulated, the entire system would flood with cold water.”

Instead of being able to run the hot-water storage tanks at 150 F, facility engineers had to turn the tanks down to produce storage temperatures of only 125 F. Also, the capacity of hot-water storage plummeted.

Digital mixing of the hotel’s domestic hot water provides exact control of water temperature at all points of use.

Enough is enough

Facility managers and engineers came together and decided to replace the entire hot-water system. Brinkerhoff was appointed to act as liaison between hotel ownership and the installing contractor. Having worked with him in the past, Brinkerhoff called on Ian Walters, project manager for Kansas City, MO-based Lexington Plumbing, a mechanical contracting firm specializing in commercial and industrial work. Walters had a solution in mind shortly after speaking with Brinkerhoff about the hotel’s water issues.

“Ian and I had this discussion about the hotel’s domestic water system, and that there are just so many dynamic changes with the pumps and water pressures,” said Brinkerhoff. “We knew what the hotel needed was a smarter, more responsive valve–especially considering that the guests in all 384 rooms had very different schedules.”

Months earlier, Walters had learned about a digital mixing valve made by Powers, a Watts Brand, North Andover, MA.

“They make a smart-delivery solution for mixing domestic water in a hot-water recirculation loop,” explained Walters. “It’s called IntelliStation. Shortly after learning about them from our rep, we installed one at a large hotel on the other side of town. There, we exceeded the expectations of facility managers–a strong confirmation that the technology worked well.”

Walters didn’t want Brinkerhoff to just take his word for it. He wanted to show him first-hand.

Joel Ryun, Lexington Plumbing, checks measuring amp draw at the system’s main control.

“I went with Ian to another Marriott hotel that had similar hot-water issues,” Brinkerhoff said. “They’d installed an IntelliStation digital mixing system there, and I was able to see it in operation and speak to facility managers who more than vouched for the system.”

What he learned was that the hotel, which had experienced similar hot-water issues, now had a fast-responding, safe, and clean domestic-hot-water system that delivered hot water on demand.

“After hearing maintenance managers validate the technology–testifying that it only took seconds for hot water to get to taps–I was sold,” added Brinkerhoff.

The Powers IntelliStation touchscreen control operates a three-way valve through a high-speed actuator to precisely maintain the selected outlet temperature. Temperature and pressure sensors are included at key points within the panel to enable an immediate response to changes in fixture demand-and-supply water conditions. A built-in optional pump provides recirculation of the tempered-water loop. This reduces the wait time at point-of-use fixtures and conserves water.

The system’s sanitization mode allows buildings with a thermal-eradication protocol in place to control water-borne bacteria to deliver a higher water temperature for a pre-set duration to allow building maintenance staff sufficient time to open all of the fixtures. IntelliStation can be connected to a building-automation system to provide ready access to a range of temperature and pressure measurements and allow adjustment of the outlet temperature setting within a pre-programmed range. BACnet IP, BACnet MSTP, and Modbus protocols are all supported.

Sizing and specifying a digital mixing station is relatively simple, with key parameters that include overall gpm, load of the building, pipe sizes, height of the structure, number of rooms and fixtures, and size of utilities such as the laundry and kitchen facilities.

Designers of large plumbing systems are discovering that a digital mixing system is the most effective way to deliver properly mixed water throughout a hot-water recirculation loop.

Digital mixing allows engineers or facility managers to select a desired hot-water temperature and to control and monitor the entire water-distribution system. For even greater control, these systems can be installed as part of an ASSE-compliant (American Society of Safety Engineers, Park Ridge, IL) water-distribution system, including point-of-use mixing valves at each fixture in the plumbing system. This ensures that hot-water storage temperatures can be kept at levels lethal to pathogens, and then mixed to safer temperature levels at points of distribution and use. Most systems are also field-configurable without the need for a laptop or special software.

Since the installation of digital mixing technology at the Kansas City hotel, facility managers have yet to receive a hot-water complaint–with hot water arriving at taps and showers quickly and at a safe, consistent temperature.

Varying pressures and temperature fluctuations throughout the hotel’s hot-water system no longer pose a threat. While 125 F water is sent to guest rooms in an instant, a second hot-water loop runs 150 F water to the kitchen and laundry areas where higher temperatures are needed for cooking and cleaning, and water is safely generated and stored at a germ-scorching 175 F.

Rather than experiencing the constant headache of boiler room problems and system troubleshooting, Brinkerhoff and his staff merely schedule routine maintenance checks on a six-month cycle.

Brinkerhoff said guests are happy. “And when guests are happy, building owners are happy,” he added. “There are no mixed emotions or mixed opinions on this investment.”

Risks For Large Domestic Water Systems

Legionella: According to the Centers for Disease Control, Atlanta, proper maintenance of water-distribution systems is key to preventing illness from water-borne bacteria such as Legionella. CDC statistics show that 8,000 to 18,000 people are hospitalized with Legionnaires’ disease in the U.S. each year. Managers of commercial and institutional facilities know that selecting and controlling proper water temperature in their storage and delivery systems plays an important part in preventing germ growth.  

Scalding: Uncontrolled and unmonitored water-distribution systems can create high-temperature scalding hazards in bathtubs, sinks, and showers. Digital mixing systems make it easy to select and set safe water temperatures for large domestic water systems.  

Thermal Shock: The thermal shock of a rapid and uncomfortable change in shower water temperature can cause a fall or serious injury. With digital mixing, stable mixed water is delivered to ASSE (American Society of Safety Engineers, Park Ridge, IL)-listed thermostatic point-of-use devices (shower or sink valves) to minimize this risk.


— Watch a video.

— Download a brochure on IntelliStation.